Series FS10-C
Flow Switch
Sizes: For pipes 1" - 6" (25 – 150mm)
Series FS10-C Flow Switch provides accurate monitoring of
liquid flow in pipelines servicing water systems, heating systems,
air conditioning, and processing installations for industrial and
commercial applications. The flow switch is designed to act as
an automatic control or safety device for liquid flow. The single-
pole, double-throw switch can be wired to start or stop a motor
when a flow or no flow condition exists or activate an alarm
when flow is inadequate. The switch then turns off the alarm
when adequate flow is restored. Series FS10-C flow switches
install in tee in horizontal or vertical piping.
Features
• Beryllium copper paddle
• Single cover retaining screw mounted on top of flow switch
• Coarse and fine sensitivity adjustment
• Two electrical conduit knockouts
• Easy accessibility to switch terminals
• 1" (25mm) NPT connection
Switch assembly independent/removable from
mounting adaptor
Optional flow indicator light integral with switch cover
(FS10-CL)
Models
FS10-C-standard unit
FS10-CL-features indicator light
FS10-CL-SS-features stainless steel bellows and paddle
Standards
Underwriter’s Laboratories Listed U.S.A. No. 11S1
Pressure-Temperature
Maximum Working Pressure: 175psi (12.1 bar) at 300°F
(148.9°C)
Maximum Temperature: 300°F (148.9°C)
For Residential and Commercial Applications
ES-FS10-C
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
Paddles
3 in 1 Paddle – A segmented beryllium copper paddle is
quickly adaptable for 1" through 3" pipe (25 through 80mm).
The extended beryllium copper paddle, also included, is for
larger pipe sizes up to 6" (150mm). Paddle length conforms
to ASTM tee standards.
Materials
Body: Brass
Enclosure: Zinc plated steel
Cover: Epoxy coated steel
Bellows: Brass ASTM B-36
Inlet Adapter: Brass ASTM B-36
Paddle: Beryllium Copper ASTM B-194
EASY WIRING
– cover
completely removable, no
danger of wires interfering
with operation.
INDEPENDENT
Switch
assembly
SWITCH
Single pole,
double throw
TWO KNOCKOUTS
Connect conduit at
either side of chassis.
O-RING INLET ADAPTER
Threaded connection
(quick paddle orientation
in pipe.)
PADDLE – made of beryllium copper.
Segmented and quickly adaptable for
1" (25mm) to 3" (80mm) pipe. Extended
paddle also included for larger pipe size.
HIGH
(Coarse)
Sensitivity
Adjustment
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
GENERAL
SIGNALING
EQUIPMENT
11S1
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Series FS10-C

Series FS10-CFlow SwitchSizes: For pipes 1" - 6" (25 – 150mm)Series FS10-C Flow Switch provides accurate monitoring ofliquid flow in pipelin

Seite 2 - Dimensions

Flow RatesFLOW RATES Required to Actuate the No. FS10C or FS20 Flow Switch in Horizontal Pipe. Flow rates in U.S. gallons per minute (GPM). Velocity i

Kommentare zu diesen Handbüchern

Keine Kommentare