Watts 709DCDA Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Zubehör fürs Wasser Watts 709DCDA herunter. Watts 709DCDA User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 4
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Check Assembly Module
Features a modular design concept which facilitates complete
maintenance and assembly by retaining the spring load.
First and second check valve spring modules are not inter-
changeable.
For Non-Health Hazard Applications
ES-709DCDA
Job Name
–––––––––––––––––––––––––––––––––––––––––––
Contractor
––––––––––––––––––––––––––––––––––––––––––––
Job Location
–––––––––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Engineer
–––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No.
–––––––––––––––––––––––––––––––––––
Approval
–––––––––––––––––––––––––––––––––––––––––––––
Representative
––––––––––––––––––––––––––––––––––––––––
IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES
FOR LOCAL INSTALLATION REQUIREMENTS
709DCDAOSY
Now Available
WattsBox Insulated Enclosures.
For more information, send for literature ES-WB.
Series 709DCDA
Double Check Detector Assemblies
Sizes: 3" – 10" (80 – 250mm)
Series 709DCDA Double Check Detector Assemblies are
designed exclusively for use in accordance with water authori-
ty containment requirements. It is mandatory to prevent the
reverse flow of fire protection system substances, i.e. glycerin
wetting agents, stagnant water and water of non-potable qual-
ity from being pumped or siphoned into the potable water line.
Benefits: Detects leaks . . . with emphasis on the cost of unac-
countable water; incorporates a meter which allows the water
utility to:
detect leaks underground that historically create great annual
cost due to waste.
provide a detection point for unauthorized use. It can help
locate illegal taps.
Modular check design concept facilitates maintenance and
assembly access. All sizes are standardly equipped with
resilient seated OSY shutoff valves,
5
8" x
3
4" (16 x 19mm) meter and ball type test cocks.
Features
Body construction fused epoxy coated cast iron
Replaceable bronze seats
Maximum flow at low pressure drop
Compact for economy combined with performance
Design simplicity for easy maintenance
Furnished with
5
8" x
3
4" (16 x 19mm) bronze meter
No special tools required for servicing
Specifications
A Double Check Detector Assembly shall be installed on fire
protection systems when connected to a potable water sup
-
ply. Degr
ee of hazard present is determined by the local
authority having jurisdiction. The unit shall be a complete
assembly including UL listed resilient seated OSY shutoff
valves and test cocks. The unit shall be UL/FM approved with
UL/FM approved OSY shutoff valves. The auxiliary line shall
consist of an approved backflow preventer and water meter.
The assembly shall meet the basic requirements of ASSE
1048; AWWA Std. C510 for Double Check Valves. Approved
by the Foundation for Cr
oss-Connection Control and Hydraulic
Research at the University of Southern California. Assembly
shall be a Watts Regulator Company Series 709DCDA.
Check Assembly
Module
Test Cock
Cover
Seat
Disc
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact W
atts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - Series 709DCDA

Check Assembly ModuleFeatures a modular design concept which facilitates completemaintenance and assembly by retaining the spring load.First and secon

Seite 2

Pressure – TemperatureTemperature Range: 33˚F – 110˚F (0.5˚ – 43˚C) continuous, 140˚F (60˚C) intermittentMaximum Working Pressure: 175psi (12.1bar)Sta

Seite 3

***********kPa psi96 1469 1041 614 2000 100 200 300 400 gpm0380 760 1140 1520 lpm5 7.5 15 fps1.5 2.3 4.6 mpsPressure DropFlowFlowFlowFlowFlow****3&quo

Seite 4

For additional information, visit our web site at: www.watts.comES-709DCDA 0638 © 2009 WattsUSA: 815 Chestnut St., No. Andover, MA 01845-6098; www.